- Use hydrostatic testing in preference to pneumatic testing wherever the system allows.
- Establish exclusion zones around all equipment before applying any test pressure.
- Follow the approved test specification for pressure, duration, and acceptance criteria.
- Ensure all test equipment is rated for the maximum test pressure being applied.
- Verify end caps, flanges, and thrust blocks are designed for the test pressure load.
- Raise pressure gradually in stages with hold points to check for leaks at each step.
- Ensure a competent person supervises the test and controls the pressurisation process.
- Record all test data including pressures, times, temperatures, and pass/fail results.
- Vent pressure safely through designated relief points after the test is complete.
- Brief all nearby workers on the exclusion zones and the test schedule before starting.
|
- DON'T use pneumatic testing when hydrostatic testing is feasible and permitted.
- DON'T allow anyone within the exclusion zone while the system is under test pressure.
- DON'T deviate from the approved test specification for pressure or duration.
- DON'T use hoses, gauges, or pumps rated below the maximum test pressure.
- DON'T rely on temporary end caps that are not designed for the test pressure load.
- DON'T apply full test pressure in a single step — increase gradually with leak checks.
- DON'T carry out a pressure test without a competent person supervising the process.
- DON'T accept a test result without documented records of all parameters.
- DON'T release test pressure suddenly — vent gradually through controlled relief points.
- DON'T enter the exclusion zone until pressure is fully released and the system is depressurised.
See also: Pipe Fitting and Flange Safety | Hydrostatic Pressure Testing
|