Pressure Testing Safety

Toolbox Talk Record

Ref: TBT-MEC-003  |  Issue: 1  |  Date: March 2026
PresenterProject
LocationDate

What?

Why?

Explosive failureA fitting failing under pneumatic test pressure releases energy equivalent to an explosion — exclusion zones are non-negotiable.
Hydrostatic preferredWater stores far less energy than gas at the same pressure — hydrostatic testing is always safer when the system allows it.
Gradual pressurisationApplying full pressure in one step can cause sudden catastrophic failure — staged pressure build-up catches leaks early.
Do Don't
  • Use hydrostatic testing in preference to pneumatic testing wherever the system allows.
  • Establish exclusion zones around all equipment before applying any test pressure.
  • Follow the approved test specification for pressure, duration, and acceptance criteria.
  • Ensure all test equipment is rated for the maximum test pressure being applied.
  • Verify end caps, flanges, and thrust blocks are designed for the test pressure load.
  • Raise pressure gradually in stages with hold points to check for leaks at each step.
  • Ensure a competent person supervises the test and controls the pressurisation process.
  • Record all test data including pressures, times, temperatures, and pass/fail results.
  • Vent pressure safely through designated relief points after the test is complete.
  • Brief all nearby workers on the exclusion zones and the test schedule before starting.
  • DON'T use pneumatic testing when hydrostatic testing is feasible and permitted.
  • DON'T allow anyone within the exclusion zone while the system is under test pressure.
  • DON'T deviate from the approved test specification for pressure or duration.
  • DON'T use hoses, gauges, or pumps rated below the maximum test pressure.
  • DON'T rely on temporary end caps that are not designed for the test pressure load.
  • DON'T apply full test pressure in a single step — increase gradually with leak checks.
  • DON'T carry out a pressure test without a competent person supervising the process.
  • DON'T accept a test result without documented records of all parameters.
  • DON'T release test pressure suddenly — vent gradually through controlled relief points.
  • DON'T enter the exclusion zone until pressure is fully released and the system is depressurised.

See also: Pipe Fitting and Flange Safety | Hydrostatic Pressure Testing