- Follow a written test procedure specifying pressure, hold time, and acceptance criteria
- Establish exclusion zones that account for the stored energy of the compressed gas
- Evacuate all personnel from the exclusion zone before pressurising the system
- Raise pressure in controlled incremental stages with visual and audible checks at each step
- Use dry nitrogen or oil-free compressed air as the test medium — never oxygen
- Ensure all connections, joints, and end caps are rated for the test pressure
- Use calibrated pressure gauges to monitor the test and confirm the hold period
- Check for leaks using soap solution or gas detection once the test pressure is achieved
- Depressurise the system fully before approaching to investigate any anomalies
- Record the test results including pressure, duration, temperature, and any leaks found
|
- DON'T allow anyone inside the exclusion zone during pneumatic pressurisation
- DON'T use oxygen for pneumatic testing under any circumstances — it creates fire risk
- DON'T raise pressure rapidly — use controlled incremental stages with checks
- DON'T approach the system to investigate leaks while it remains pressurised
- DON'T use fittings, valves, or end caps not rated for the pneumatic test pressure
- DON'T conduct a pneumatic test where a hydrostatic test is practicable and safer
- DON'T leave a pressurised system unattended without continuous monitoring
- DON'T apply the full test pressure without first holding at intermediate stages
- DON'T ignore small leaks — depressurise, repair, and retest before acceptance
- DON'T underestimate the stored energy — pneumatic failures are far more violent than hydraulic
See also: Hydrostatic Pressure Testing | Pressure Testing Safety
|